- Catalog
- INSTALLATION DEVICES
- Motor Protective Circuit Breakers
- Manual motor starter Ex9SN25B10A
Manual motor starter Ex9SN25B10A
108949
8592765089496
Manual motor starters are electromechanical protection devices for the main circuit. They are used mainly to switch motors manually ON/OFF and protect them fuseless against short circuit and loss-phase. Fuseless protection with a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by switching off the motor within milliseconds. Manual motor starter combinations are setup together with contactors and overload relays.
| Overload release current setting [A] | 6-Oct |
| Adjustment range undelayed short-circuit release [A] | 138 |
| Thermal protection | Yes |
| Phase failure sensitive | Yes |
| Switch off technique | Thermomagnetic |
| Rated operating voltage [V] | 230-690 |
| Rated permanent current Iu [A] | 10 |
| Rated operation power at AC-3, 230 V [kW] | 2.2 |
| Rated operation power at AC-3, 400 V [kW] | 4 |
| Type of electrical connection of main circuit | Frame clamp |
| Type of control element | Push button |
| Device construction | Complete device in housing |
| With integrated auxiliary switch | No |
| With integrated under voltage release | No |
| Number of poles | 3 |
| Rated short-circuit breaking capacity Icu at 400 V, AC [kA] | 100 |
| Degree of protection (IP) | IP20 |
| Height [mm] | 81 |
| Width [mm] | 44.5 |
| Depth [mm] | 91.3 |
| Power loss [W] | 9 |