Manual motor protective circuit breaker Ex9S80A 20B

113828
8592765138286

Manual motor protective circuit breakers Ex9S80A provide overload, short-circuit and phase-failure protection for the three-phase asynchronous motors with not frequent starting. They are also suitable for power distribution line protection or can be used simply as an isolator. The right setting of adjustable overload current allows to optimize motor protection by means of circuit breaker. In case of 3P application, correct setting of Ir provides also protection against overload caused due to a phase lost. Ambient temperature compensation function reduces the impact of ambient temperature. Release testing mechanism enables to test the function of the system and control rotary knob lock mechanism prevents illegal operation. Motor protective circuit breakers can be combined with wide range of accessories including auxiliary and signal contacts, shunt trip and undervoltage releases. It is possible to create diverse combination of accessories.

Overload release current setting [A]14- 20
Adjustment range undelayed short-circuit release [A]-
Thermal protectionYes
Phase failure sensitiveYes
Switch off techniqueThermomagnetic
Rated operating voltage [V]400 - 690
Rated permanent current Iu [A]20
Rated operation power at AC-3, 230 V [kW]4
Rated operation power at AC-3, 400 V [kW]7.5
Type of electrical connection of main circuitFrame clamp
Type of control elementTurn button
Device constructionComplete device in housing
With integrated auxiliary switchNo
With integrated under voltage releaseNo
Number of poles3
Rated short-circuit breaking capacity Icu at 400 V, AC [kA]100
Degree of protection (IP)IP20
Height [mm]140
Width [mm]55
Depth [mm]137
Power loss [W]4.3